Audience: presenter · Profile: demo · Read this when: you are setting up a rep machine to read an OT cell through its PRA protocol tunnels.

How to set up a Windows laptop to read an OT Demo Cell through its PRA protocol tunnels, and what to type in front of a customer. Four Python clients cover the four protocols the cell simulates — pymodbus, asyncua, pylogix and python-snap7 — and all four install as plain wheels with no native toolchain, no vendor runtime and no licence.

If you would rather demo with a GUI, UaExpert and QModMaster are covered at the end. Start here regardless: the scripted check is what tells you the cell is healthy before you share your screen.

What you actually need

Why
PRA representative console The only thing that creates the tunnel. Download it from your appliance's /login → My Account. A Protocol Tunnel Jump listens on 127.0.0.1:<local port> only while the session is running; closing it closes the listener
Python 3.9+ python.org or the Microsoft Store. py --version should answer
Four pip packages Below. ~20 MB total, no admin rights needed

You do not need Docker, WSL, admin rights, or a vendor SDK. Unlike Linux, Windows does not reserve ports below 1024, so the tunnels on :102 and :502 bind as a normal user.

Install

In PowerShell:

py -m venv $HOME\ot-clients
& $HOME\ot-clients\Scripts\python.exe -m pip install --upgrade pip
& $HOME\ot-clients\Scripts\python.exe -m pip install "pymodbus>=3.6.8" "asyncua>=2.0.1" pylogix "python-snap7>=3.1.2"

Calling python.exe by full path skips Activate.ps1, which needs an execution-policy change on a locked-down build. If you would rather activate the venv once per shell:

Set-ExecutionPolicy -Scope Process -ExecutionPolicy RemoteSigned; & $HOME\ot-clients\Scripts\Activate.ps1

Check it took:

& $HOME\ot-clients\Scripts\python.exe -c "import pymodbus, asyncua, pylogix, snap7; print('ready')"

Behind a TLS-inspecting proxy (Zscaler, Netskope, Palo Alto — the same one that breaks Docker pulls), pip fails with CERTIFICATE_VERIFY_FAILED. Point it at your corporate root CA rather than disabling verification:

$env:PIP_CERT = "C:\path\to\corp-root.crt"

The same PEM you would drop in corp-ca/.

Version notes that matter

Verify the whole cell in one command

scripts/ot/verify_tunnels.py reads all four protocols and tells you which are live. Run it after starting the cell's tunnel jump items in the representative console:

& $HOME\ot-clients\Scripts\python.exe scripts\ot\verify_tunnels.py
OK   Modbus TCP       127.0.0.1:502   Counter=216  Temperature=42.4C  Flow=104  Running=yes
OK   Siemens S7comm   127.0.0.1:102   Counter=279  Temperature=39.3C  Flow=144  Running=yes
OK   EtherNet/IP      127.0.0.1:44818 Counter=267  Temperature=37.8C  Flow=132  Running=yes
OK   OPC UA           127.0.0.1:4840  Counter=279  Temperature=39.4C  Flow=145  Running=yes

4/4 protocol(s) answered with live, moving values.

It reads each protocol twice and compares, so OK means the values are moving — not merely that something answered. The four statuses map to the four things that actually go wrong:

Means
OK Answered, and the counter advanced between samples
WARN Answered, but frozen — the sim's updater thread is wedged. The demo will show dead values
FAIL Either nothing is listening (tunnel not started, or on a different local port) or something is listening but not speaking the protocol (that sim was not baked, or its container is dead) — the message says which
SKIP You have not installed that client library. Not a failure unless you pass --strict

Useful flags: --only modbus,opcua to check a subset, --modbus-port 1502 when a jump item uses a non-default local port, --strict for a pre-demo gate that refuses to pass on anything it could not prove, and --json to script it. Exit code is 0 only when every selected protocol answered.

Reading each protocol by hand

Run these with the venv's Python, one tunnel started at a time. Every sim serves the same four process values, so the same demo story works for any vendor in the room:

Value Modbus / S7 / EtherNet-IP OPC UA
Counter increments every second, wraps at 65535 same, as Int32
Temperature degrees C × 10 as an integer (404 = 40.4 °C) real degrees C, as a Double
Flow ~120 ± 30 same, as a Double
Running always 1 true

The ×10 is not a bug: fieldbus protocols carry no unit metadata, so scaled integers are what real gear does. OPC UA is typed, so it carries the engineering value — which is itself a good thirty seconds of the demo.

Modbus TCP — 127.0.0.1:502

Holding registers 0–3, function code 3. Coil 0 also toggles every second.

from pymodbus.client import ModbusTcpClient

client = ModbusTcpClient("127.0.0.1", port=502)
client.connect()
rr = client.read_holding_registers(0, count=4, device_id=1)
print(rr.registers)          # [1234, 404, 131, 1]
client.close()

OPC UA — 127.0.0.1:4840

Anonymous, no security policy — exactly how most plant-floor OPC UA servers are actually deployed, which is the point: the network path is the control.

import asyncio
from asyncua import Client

async def main():
    url = "opc.tcp://127.0.0.1:4840/freeopcua/server/"
    async with Client(url=url) as client:
        ns = await client.get_namespace_index("http://ot-sim.demo")
        plant = await client.nodes.objects.get_child([f"{ns}:Plant"])
        for name in ("Counter", "Temperature", "Flow", "Running"):
            node = await plant.get_child([f"{ns}:{name}"])
            print(name, await node.read_value())

asyncio.run(main())

The endpoint path is /freeopcua/server/. asyncua ignores a wrong path; stricter clients refuse the connection, so get it right in any GUI you configure.

Requested session timeout to be 3600000ms, got 600000ms instead on stderr is asyncua noting that the server granted a shorter session than it asked for. It is expected and harmless — verify_tunnels.py silences it so it cannot read as a fault mid-demo.

EtherNet/IP — 127.0.0.1:44818

Four DINT CIP tags, read with pylogix — the client BeyondTrust's OT material points customers at.

from pylogix import PLC

with PLC() as comm:
    comm.IPAddress = "127.0.0.1"
    for name in ("Counter", "Temperature", "Flow", "Running"):
        ret = comm.Read(name)
        print(name, ret.Status, ret.Value)

Tag names are case-sensitive and capitalised exactly as above.

Siemens S7comm — 127.0.0.1:102

DB1, four big-endian words at offsets 0/2/4/6. S7 has no tag names — a wrong offset reads as plausible garbage rather than an error, so keep the >HHHH.

import struct, snap7

client = snap7.client.Client()
client.connect("127.0.0.1", 0, 1, tcp_port=102)
print(struct.unpack(">HHHH", bytes(client.db_read(1, 0, 8))))
client.disconnect()

Expected COTP DT, got 0x80 on stderr during connect is harmless noise from the pure-Python server; the reads still work.

Kubernetes API — 127.0.0.1:6443

Not a fieldbus protocol: this is the cell's own k3s cluster, the thing the four simulators run on. The client is kubectl, and the only setup is collecting the kubeconfig the cell writes for exactly this path — once, through the Shell Jump:

sudo cat /var/lib/ot-sim/kubeconfig-via-tunnel.yaml

Save it on the rep machine as ot-cell.yaml. It is the cell's admin kubeconfig with server: https://127.0.0.1:6443, the tunnel's local end. k3s's API certificate already names 127.0.0.1, so nothing else needs changing. With the ot-<cell>-k3s jump started (ot-<cell>-kubesolo on a cell deployed before the move to k3s):

kubectl --kubeconfig .\ot-cell.yaml get nodes
kubectl --kubeconfig .\ot-cell.yaml -n ot-sim get pods -o wide
kubectl --kubeconfig .\ot-cell.yaml -n ot-sim logs deploy/ot-plc --tail=5

The pods answer on the node's own address — that is hostNetwork, and it is why the protocol tunnels above reach them. Stop the jump and every command fails to connect, which is the point worth making out loud: the plant's cluster has no other way in.

verify_tunnels.py does not check this one; a stopped jump and a wrong kubeconfig fail differently enough to tell apart (connection refused versus a certificate error).

DNP3 — not simulated

The cell does not serve DNP3. opendnp3 needs a library built from source, which the image's every-dependency-is-a-pinned-wheel contract cannot honour, so the DNP3 preset exists for a standalone tunnel to real or lab gear. The deploy form still offers it, so if you tick DNP3 on a cell you will get a tunnel to a port with nothing behind it — which looks exactly like a blocked firewall.

Running the demo

  1. Deploy the cell and wait for the parent job to finish green (cloud page → OT tab). Tick every protocol you intend to show; each becomes its own tunnel jump item.
  2. Before the call, start the jumps and run verify_tunnels.py --strict. This is the whole reason it exists — a cell that answers now will answer in ten minutes, and a cell that does not gives you time to Re-wire or redeploy.
  3. Open with the HMI. Web Jump to FUXA on :1881 needs nothing installed and shows the plant moving. Then reveal that the VM has no public IP, no inbound rule, and no route off the plant subnet.
  4. Then the protocol. Start the tunnel jump, run the snippet for whichever vendor the customer runs, and read live values off an air-gapped PLC — through a session that is recorded and attributable.
  5. Land the point. The tunnel is generic TCP: no credential is injected on the wire, because these protocols are unauthenticated by design in most real PLCs. The network path is the control, and PRA is the only way in.

One protocol per tunnel jump, and two tunnels cannot listen on the same local port at once — so if you are switching vendors live, close one session before starting the next, or give them distinct local ports.

GUI clients (optional)

Worth installing if you want something more visual than a terminal, but none of them are required:

Protocol Client Notes
OPC UA UaExpert (Unified Automation, free with registration) Add the server as opc.tcp://127.0.0.1:4840/freeopcua/server/, anonymous, None/None security. Browse Objects → Plant
Modbus QModMaster (free) or Modbus Poll (trial) Slave 1, holding registers, start 0, quantity 4
Siemens TIA Portal PLC address 127.0.0.1 — only worth it if the customer already lives in it

Point GUI clients at 127.0.0.1 explicitly. The OPC UA sim advertises its endpoint as 0.0.0.0, and some OPC UA and EtherNet/IP stacks reconnect to whatever address the server advertises rather than the one you typed. The tunnel forwards only the brokered port, so a client that wanders off it just hangs.

Troubleshooting

Symptom Cause
verify_tunnels.py says nothing is listening, on every protocol The tunnel jumps are not started in the representative console, or the session dropped. The listener only exists for the life of the session
Nothing listening on one protocol That jump item uses a different local port — check the jump item and pass --<protocol>-port
Listener answers nothing That sim was not baked into the image (OT_SIMS selects them at bake time; an image baked before Siemens was added has no ot-s7), or its pod died. Shell Jump to the cell and run kubectl -n ot-sim get pods
Values answer but never change The sim's updater thread is wedged — kubectl -n ot-sim rollout restart deploy/ot-plc (or the sim's own deployment), or redeploy the cell
kubectl says x509: certificate is valid for …, not 127.0.0.1 You are not using the cell's /var/lib/ot-sim/kubeconfig-via-tunnel.yaml, whose server is https://127.0.0.1:6443 — a name k3s's certificate covers. (A cell deployed on KubeSolo wrote a tls-server-name into that file instead; it still works)
The tunnel will not bind the local port Something else holds it: Get-NetTCPConnection -LocalPort 502. Hyper-V and WSL also reserve port ranges — netsh int ipv4 show excludedportrange protocol=tcp. Give the jump item a different local port and pass it to the script
pip fails with CERTIFICATE_VERIFY_FAILED TLS-inspecting proxy — set PIP_CERT to your corporate root CA (above)
TypeError on read_holding_registers pymodbus version drift on the unit-id kwarg — try slave=1 instead of device_id=1
OPC UA connects but browsing finds no Plant Wrong namespace or endpoint path. Resolve the index with get_namespace_index("http://ot-sim.demo") rather than hardcoding ns=2
Azure cell: Web Jump works, the tunnel never establishes The cell's Gateway resolved to an ACI gateway — ACI is serverless and cannot do protocol tunneling. See OT demo cell